When we using central controller, in the old modbus exchange table of outdoor unit, unit of set temp. is 1℃, but for our new batch VRF production, unit of set temp. is 0.5℃. So we added a new address to set IDU temp.: function code 03, address 40515.The “Set Temp.” Modbus addresses are 40515 for IDU1, 40521 for IDU2 and so on, up to 40893 for IDU64, spaced at regular intervals.