Home > Service & Support > Troubleshooting > Why the targetSH of duct type indoor unit change from 1 to -4℃?
Question: Why the targetSH of duct type indoor unit change from 1 to -4℃?
Answer:

It is because of outdoor unit protection control, for MRV5 sereial, the outdoor unit will force to open the indoor unit EEV valve wider through changing the targetSH when Td≥95℃. And when Td ≤90℃, it will exit this control, the targetSH of indoor unit will come back to 1.