We use cookies to give you the best online experience. By using our website you agree to our use of cookies in accordance with our cookie policy. Learn more here.
In store stocks availability are subject to respective retailers.
Share
Capacity
06 HP
Voltage Range
310V~460V
Working Temperature
5~ 50 ˚C
Diversity
50%~130%
Advanced Technology
Haier MRV SII adopts Two-stage supercooling cycle technology that increases outdoor unit efficiency by 9% with double fan. MRV SII Maximizing 30°C undercooling, increase unit refrigerating capacity by 46%.
High Efficiency
Haier MRV SII comes with DC Inverter Twin Rotary Compressor which provides Small Torque Change, Good Dynamic Balance, system runs stably with little vibration, very low noise can be reduced to 45dB(A), high efficiency in part load running.
DC Inverter Fan Motor
DC inverter fan motor provides higher efficiency in part load running, 16-stage speed control; high efficiency running especially in low speed, Efficiency of Outdoor unit can be increased by 45% comparing with AC motor and power input largely decreases.
Automatic Refrigerant Reclaim Technology
Haier MRV SII provides automatic refrigerant reclaim through dip switch setting, the refrigerant in indoor and pipe can be automatically return to outdoor, convenient in maintenance and reducing waste of refrigerant, reduce customer maintenance cost, improve the efficiency of after-sales maintenance.
Similar Products
My Tracks
Specification
Capacity:
06
Product Segment:
MRV Outdoor
Price:
289000
Technology:
Inverter AC
Cooling Capacity (kW):
15.5
Heating Capacity (kW):
18
Cooling Capacity (KBtu/hr.):
52.89
Heating Capacity (KBtu/hr.):
61.4
Power Supply:
1-Ph/220~240V/50Hz
Air Flow (m3/hr.):
7200
Sound Pressure Level (H) - Heating:
59
Sound Pressure Level (H) - Cooling:
59
External Static Pressure (Pa):
110
External Dimension (W/D/H) - mm:
950/370/1340
Net Weight - Kg:
108
Compressor Type:
Rotary
Compressor Qty.:
1 - DC Inverter
Refrigerant:
R-410a
Piping Connections - Liquid:
Ф9.52
Piping Connections - Gas:
Ф15.88
Max. Total Pipe Length:
300
Max. Pipe Length (Equivalent/Actual):
175/150
Max. Drop between I.D.U. & O.D.U. ( O.D.U. Down/Up):